novaPro32 Routel
novaPro32 set-up
24
7000991003 Q2
Sauter Systems
5
novaNet PC
- This is the PC address. It has to be set identical to the one in the Routel. Refer to
Chapter 3.2.
Phone Number
- The phone number of the Routel island concerned.
Refer to your modem manual for special commands (e.g. ‘,’ makes the modem wait
for 1 or 2 seconds, ‘w’ makes the modem wait for the dial tone before continuing).
Remote Supervision Mode (Routel)
- Tick needs to be set to enable the Routel mode.
Message AS and ASNet Supervision
- If set, the Routel supervises the number of AS communicating on novaNet as well
as the presence of the AS net itself. If there is any change, the Routel will call the
Supervision PC.
Æ novaPro32 will make use of this message only from Version 4.1.
Message after Power Failure novaNet291
- Causes the Routel to call the Supervision PC after a return of the Supply Power to
the Routel.
- The received "Supply Supervision Messages" are logged into the Routel logfile.
Message and Refresh after 3
rd
Party PC-Access
- If ticked, the Routel will report to the Supervision PC any access from a Remote
Access PC (mode Router) to the Routel. This, on one hand for security reasons, but
also because alarms occurring during the access of the Remote PC would be lost
on the Supervision PC (Routel memory flushed by the data reading from the
Remote Access PC).
- After the reception of a Remote Access message, the Supervision PC will
automatically call the island concerned, refreshing and thus reading all the
addresses concerned and then displaying them in the alarm list.
- The ‘Remote Access’ messages received are logged into the Routel logfile.
Screen Pop-Up after 3
rd
Party PC Access
- A Remote PC Access Message as described above will in addition be displayed as
a Pop-Up message on screen.
Time-out for connection from PC (min.)
- This entry does not concern the Routel connections. It activates a time-out on a
Remote Access Connection (PC called 291).
- The time-out is armed at the moment of the connection (not after the last
keyboard/mouse activity).
- After the time-out, a message is displayed to warn the user that the connection will
be disconnected in 60 seconds. A button is available with this warning, which can
be used to re-arm the time-out if desired.
- A time-out value of 0 minutes disables the time-out feature.
Comentarios a estos manuales