ZyXEL Communications PLA-470 V2 - V3.0.5 Guía de instalación Pagina 164

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 349
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 163
are major components of an electrical network for the PLC signal since they sepa-
rate the public electrical network from the electrical network of a building, of an
apartment, or of a company.
Most meters allow the PLC signal to pass on each side of the electrical network.
Therefore, it is important to correctly configure the PLC local area network encryp-
tion if the interception by a malevolent person of data flowing over the electrical
network is to be avoided.
Electromechanical meters are the oldest ones. These meters, dating from the
seventies, are very frequently encountered in electrical equipment. They allow the
PLC signal to pass on either side of the electrical circuit. Their evaluated PLC signal
attenuation is 20 dB.
Electromechanical meters were gradually replaced during the 1990s by elec-
tronic counters to prevent piracy. These meters, whose piracy is very difficult, are
used for remote meter readings via the EDF network using the very low rate, low
frequency PLC technology. They also allow the PLC signal to be transmitted. Their
evaluated PLC signal attenuation is 15 dB.
Repeaters
Repeaters are devices frequently used in telecommunications to regenerate the data
transmission signal when the distances are too long for the received signal to be
usable by the data transmission devices.
In the case of PLC networks, the electrical network causes attenuations of the
PLC signal (circulation of electrical network components, noises of the connected
devices, quality of the electrical wirings, and so forth) that sometimes make it
impossible to obtain a PLC link between two distant points of the network without
signal repetition.
There are two types of repeaters: passive repeaters and active repeaters. Passive
repeaters regenerate the PLC signal by using two PLC chips relaying the signal from
one chip to the other one. Repeating takes place both at the physical layer and MAC
layer levels. Active repeaters amplify the PLC signal on the electrical wiring without
using another PLC chip to relay the signal. Repeating only takes place at the physi-
cal layer level.
Figure 7.28 gives an example of repeater use.
Few repeaters can be found in stores since the PLC signal can be satisfactorily
broadcast using PLC devices. However, it may be interesting to repeat the PLC sig-
nal to obtain suitable bit rates over the entire electrical network.
The following PLC repeaters are available in stores:
Schneider IR LR 1100;
Asoka PL8230-2RP (active);
Oxance PLT300, PLT320 (active);
CMM RPT1-0.
Repeaters 145
Vista de pagina 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 348 349

Comentarios a estos manuales

Sin comentarios